A Comparative Analysis Power Losses At The Connection Point Of Tap Connectors With Joint Press Connectors On Low Voltage Network East Binjai Customer Service Unit (ULP)

  • Mira Yolanda Br Sembiring Universitas Pembangunan Panca Budi, Medan, North Sumatera, Indonesia
  • Dicky Lesmana Universitas Pembangunan Panca Budi, Medan, North Sumatera, Indonesia
  • Zulkarnain Lubis Universitas Pembangunan Panca Budi, Medan, North Sumatera, Indonesia
Keywords: Power Losses, Connector Tap Connection Point, Connector Joint Press, (JTR)

Abstract

In the electric power distribution network or a condition where a distribution system in the distribution of electric power experiences high power losses due to the connection point on the distribution cable to the consumer. Therefore, in this study, a calculation will be carried out between the value of the comparison of the input and output measurements between the connection points using Tap Connector with Joint Press Connector, after obtaining the measurement results, determine the calculation results for the loss of electrical power energy in rupiah units. A Tap Connector Joint Press Connector. After the measurement and calculation, the Power Loss is the result of the calculation between the input and output at the Tap Connector connection point. There is a difference in Power Loss of 134.3 Watts while at the Joint Press Connector the Power Loss Difference is 0 Watts. Power Loss Calculation Results in Rupiah Units From the results of the power loss analysis calculation, it can be seen that the power loss at the Tap Connector connection point with a difference in power loss value of 134.3 W and if calculated in rupiah units, then the loss of electrical energy in one month is Rp. 130,539.6, -. If it occurs in one year in a 24-hour time calculation, it is 130,539.6 x 12 Months = 1,566,475.2, -. The cause of power loss at the Tap Connector connection point is due to poor installation, as well as Tap Connector Equipment that is not SPLN standard and the age of the Tap Connector that has worn out

Downloads

Download data is not yet available.

References

[1] Hamles L. Latupeirissa, Halamoan M. Muskita, Critter A, Leihitu, 2018 “Voltage Loss Analysis in Low Voltage Network (Jtr) 380/220 Volt Distribution Substation of Am-bon State Polytechnic” SYMMETRIC JOURNAL VOL.8, NO.1, JUNE 2018. p-ISSN: 2302-9579/e-ISSN: 2581-2866
[2] Ahmad Syaifuddin F, Arief Budi Laksono, Suharijanto.2018 “Comparative Analysis Study of Power Loss at Piercing Connector Connection Point with Line Tap Con-nector on Low Voltage Network” JE: Electronic Control, Telecommunication, Com-puter Information and Power Systems. ISSN: 2502-0986 | Vol 3 No 1 March 2018
[3] Winda Puspitasari, Arfitariah, Hardianto. 2023 “Distribution Transformer Maneuver At PT.PLN (Persero) Customer Service Unit Bontang City With Transformer Muta-tion” Journal Of power electric and renewable Energy (JPER). Vol. 1No. 2. Decem-ber2023P-ISSN 2986-8335E-ISSN 2987-0100
[4] Asfihanuddin Muhtar, Iwan, Dr. Ir. H. Antarissubhi, Suryani. 2021 “Analysis of Pri-mary Distribution Network Power Loss of PT. Pln ULP Sengkang, South Sulawesi”. Vertex Elektro, Vol.13, No.01, Year 2021 (February) p-ISSN. 1979-9772 e-ISSN. 2714-7487
[5] Aldila Fajar Rizkiana, Yuris Mulya Saputra. 2024 “Improvement of Voltage Drop and Power Loss by Reconfiguring the House Connection Network and Reconducting the Low Voltage Network at the MI-44-150-21 Distribution Substation of PT PLN ULP Magelang City”. Journal of Electrical, Instrumentation, and Applied Electronics, Vol. 5, No. 1, April 2024
[6] Oktavianus Kati, Am Khafabin, Suparno. 2021 “Evaluation Study of Low Voltage Network Distribution (JTR) at JPR 047 Substation, Merak Feeder”. Jurnal EL Sains Volume 3, Number 1, July 2021 E-ISSN: 2656-7075- P-ISSN: 2527-6336
[7] Harsen Nimpa, Heru Sutejo. 2018 “Development of Android-Based PLN Distribu-tion Substation Measurement Information System” 2018 National Conference on Information Systems STMIK Atma Luhur Pangkalpinang, 8 – 9 March 2018
[8] Muhammad Irsyam, Missyamsu Algusri, Linggom Pandapotan Marpaung. 2023 “Analysis of Power Losses in Low Voltage Network of PT. Musimmas Batam” Sig-ma Teknika, Vol. 6, No.1 : 109-119 June 2023 E-ISSN 2599-0616 P ISSN 2614-5979.
[9] Aryza. S, Wibowo. P & Saputra. D (2022, July). ‘ Rancang Bangun Alat Pengontro-lan Proses Pemanasan Produksi Biodiesel dari minyak jelantah berbasis Arduino mega. In prosiding seminar nasional social humaniora dan tekhnologi ( PP. 121-127)
[10] Anisah, S., Fitri, R., Taro, Z., & Wijaya, R. F. (2022). Comparison of Lighting Efficien-cy (Led-CFL) based on Environmentally Friendly Technology. Journal of Applied Engineering and Technological Science (JAETS), 4(1), 568-577.
[11] Hamdani, H., Tharo, Z., Anisah, S., & Lubis, S. A. (2020, September). Rancang Bangun Inverter Gelombang Sinus Termodifikasi Pada Pembangkit Listrik Tenaga Surya Untuk Rumah Tinggal. In Prosiding Seminar Nasional Teknik UISU (SEMNASTEK) (Vol. 3, No. 1, pp. 156-162).
Published
2024-10-04
How to Cite
Mira Yolanda Br Sembiring, Dicky Lesmana, & Zulkarnain Lubis. (2024). A Comparative Analysis Power Losses At The Connection Point Of Tap Connectors With Joint Press Connectors On Low Voltage Network East Binjai Customer Service Unit (ULP). Jurnal Scientia, 13(04), 1487-1494. Retrieved from http://seaninstitute.org/infor/index.php/pendidikan/article/view/2632

Most read articles by the same author(s)